22 min read#fsae#tech#electrical

FSAE Shutdown Circuit Guide

Bbrianteh
FSAE Shutdown Circuit Guide

FSAE Shutdown Circuit (SDC): Complete Design Guide

Scope: Formula SAE Electric (EV) vehicles, with notes for Combustion (IC) where the rules overlap. Important: Rule numbers below follow the 2021 FSAE rules layout (T.3.2, EV.7.7, EV.8.x). Rule numbering and some thresholds are reorganized in later years and differ between FSAE, Formula Student (FSG/FSUK) and Formula Hybrid+Electric. Always verify against your competition's current rulebook.


Table of Contents

  1. What is the shutdown circuit?
  2. Design philosophy
  3. Architecture overview
  4. Component-by-component breakdown
  5. Master switches (GLVMS and TSMS)
  6. Shutdown buttons (BRBs)
  7. BOTS: Brake Over-Travel Switch
  8. Inertia switch
  9. BSPD: Brake System Plausibility Device
  10. IMD: Insulation Monitoring Device
  11. AMS / BMS
  12. Interlocks (HVD, TSMP access, etc.)
  13. Accumulator isolation relays (AIRs)
  14. Latching and reset behavior
  15. Wiring, fusing and power budget
  16. Startup sequence
  17. Fault matrix
  18. Technical inspection (scrutineering) checklist
  19. Common mistakes and failure modes
  20. Design and validation checklist
  21. Glossary
  22. Images and references

1. What is the shutdown circuit?

The Shutdown Circuit (SDC), also called the shutdown loop or safety loop, is a series chain of safety switches and monitoring devices that powers the coils of the Accumulator Isolation Relays (AIRs). If any element in the chain opens, the AIRs de-energize and the high-voltage (HV) Tractive System (TS) is disconnected from the accumulator.

In one sentence: the SDC is a hardware-enforced "dead man's chain" that guarantees the car's high voltage drops out whenever something unsafe is detected.

Key facts:

  • It is a series circuit: every device must be "closed" for the circuit to stay closed.
  • It operates on the GLV (Grounded Low Voltage) side (typically 12 V nominal, 24 V on some cars).
  • It is fail-safe: loss of power, a broken wire or a failed component results in an open circuit, which means HV off.
  • It is built from simple, mostly analog/mechanical parts so its behavior is deterministic and easy to inspect.

Shutdown circuit overview Figure 1: Replace with your team's SDC schematic or the rulebook diagram (see Section 22).


2. Design philosophy

Principle What it means in practice
Fail-safe Open circuit = safe state. Relays are normally open, so power must be deliberately applied to close them.
Series logic Any single fault opens the loop. There is no voting and no bypass.
Hardware first Critical functions (BOTS, BSPD, IMD, AMS outputs) must not depend on software that could hang.
Latching Faults from the IMD and AMS stay latched until a manual reset (not by the driver).
Independence The SDC must keep working even if the main ECU or VCU crashes.
Inspectable Tech inspectors need to be able to trace and test each element.

A shutdown circuit being open does not mean the car is safe to touch. The TS must still be verified de-energized with the TSMPs and discharge circuit.


3. Architecture overview

3.1 Typical series chain

GLV battery / DC-DC
      |
   [ GLVMS ]  ──► (powers entire GLV system)
      |
   [ Cockpit BRB ]
      |
   [ Left BRB ]
      |
   [ Right BRB ]
      |
   [ BOTS ]
      |
   [ Inertia switch ]
      |
   [ BSPD (relay/output) ]
      |
   [ IMD (relay/output) ]
      |
   [ AMS / BMS (relay/output) ]
      |
   [ Interlocks: HVD, etc. ]
      |
   [ TSMS ]   ◄── last switch before the AIRs (except precharge and interlocks)
      |
   [ AIR+ coil ] ── [ AIR- coil ]
      |
     GND

Order of the elements varies by team. The rules mandate what must be in the loop and a few ordering constraints (for example, the TSMS being the last switch before the AIRs), not a single layout.

3.2 Mermaid diagram

flowchart LR
    BAT[GLV Battery + DC/DC] --> GLVMS[GLVMS]
    GLVMS --> BRB1[Cockpit BRB]
    BRB1 --> BRB2[Left BRB]
    BRB2 --> BRB3[Right BRB]
    BRB3 --> BOTS[BOTS]
    BOTS --> INERTIA[Inertia Switch]
    INERTIA --> BSPD[BSPD]
    BSPD --> IMD[IMD]
    IMD --> AMS[AMS / BMS]
    AMS --> IL[Interlocks]
    IL --> TSMS[TSMS]
    TSMS --> AIRP[AIR+ coil]
    TSMS --> AIRN[AIR- coil]
    AIRP --> GND((GND))
    AIRN --> GND

3.3 Where each part lives on the car

Device Typical location
GLVMS, TSMS Right side of the car, near the main hoop, at driver's shoulder height
Cockpit BRB Within easy reach of the belted driver, near the steering wheel/dash
Side BRBs Left and right of the car behind the driver, reachable by marshals
BOTS At the brake pedal assembly
Inertia switch Mounted rigidly to the chassis, usually near the driver's cell/accumulator
BSPD, IMD, AMS In or near the accumulator container or low-voltage electronics box
Interlock switches HVD connector, accumulator lid, TS enclosure covers

Shutdown circuit component locations Figure 2: Car layout showing shutdown component placement.


4. Component-by-component breakdown

# Component Purpose Opens SDC when… Reset
1 GLVMS Kills all GLV power Key turned OFF Manual (key)
2 BRBs (x3) Emergency stop Button pressed Manual pull/twist
3 BOTS Detect brake failure/over-travel Pedal exceeds normal travel Cannot be reset by driver
4 Inertia switch Detect crash High deceleration Manual reset
5 BSPD Detect hard braking + high power Plausibility violated Manual (not driver)
6 IMD Detect HV insulation fault Insulation resistance below threshold Manual (not driver)
7 AMS/BMS Protect the accumulator Cell over/under-voltage, over-temperature, over-current, comms loss Manual (not driver)
8 Interlocks Prevent HV with covers/connectors open Connector unplugged or lid removed Restoring the mechanical condition
9 TSMS Master HV enable Key OFF Manual (key)

5. Master switches (GLVMS and TSMS)

From the 2021 rules (EV.8.10), each car has two master switches.

5.1 GLVMS (Grounded Low Voltage Master Switch)

  • Must completely stop all power to the GLV system.
  • Located in the center of a red circular area, >50 mm diameter.
  • Labeled "LV".

5.2 TSMS (Tractive System Master Switch)

  • Must open the Shutdown Circuit.
  • Must be the last switch before the AIRs (except precharge circuitry and interlocks).
  • Located in the center of an orange circular area, >50 mm diameter.
  • Labeled "TS" with the ISO 7010-W012 high-voltage symbol (black lightning bolt in a yellow triangle).
  • Must support lockout/tagout.

5.3 Requirements common to both

  • Direct acting: not through a relay or logic.
  • Mounted on the right side, near the main hoop, at driver's shoulder height.
  • Easily actuated from outside the vehicle.
  • Rotary mechanical type with a red removable key, removable only in the OFF position.
  • Rigidly mounted, not removed during maintenance.
  • Rotary axis near horizontal and across the vehicle.
  • ON position horizontal and clearly marked; OFF clearly marked.

GLVMS and TSMS layout Figure 3: Master switch placement and marking.


6. Shutdown buttons (BRBs)

The "Big Red Buttons" are the emergency stops.

  • A car needs three: one in the cockpit and one on each side of the car behind the driver.
  • Red, clearly marked, mechanical, direct acting (they physically break the SDC current path).
  • Typically push-to-open / twist-or-pull-to-reset.
  • Must be reachable by track marshals without crossing the driver's space.
  • Usually marked with a lightning/shutdown sign per the rulebook.

Design tips

  • Use normally-closed (NC) contacts. A broken wire then equals an open SDC.
  • Choose a button with a positive-opening contact block (contacts are forced apart).
  • Check the contact rating for the SDC current plus inductive spikes.

7. BOTS: Brake Over-Travel Switch

From T.3.2:

  • Installed so brake pedal travel beyond the normal range actuates it.
  • A mechanical single-pole single-throw switch (push-pull or flip type).
  • Operating it to OFF must:
    • (IC) shut down the engine(s) and fuel pump(s).
    • (EV) open the Shutdown Circuit.
  • Repeated operation must not reset or restore power.
  • The driver cannot reset it.
  • Must be implemented with analog components, not PLCs, ECUs or similar digital controllers.

Why it exists: if a brake pedal, linkage or master cylinder fails and the pedal over-travels, the car must shut down immediately.

Design tips

  • Mount the switch so it is actuated by the pedal itself or its mount, not a separate tab that can flex.
  • Add a latch (a relay with a self-hold) if "repeated operation must not reset" is a concern, and confirm that approach with your rulebook.
  • Test with the pedal fully extended and with a deliberately failed linkage.

8. Inertia switch

  • Detects abnormal deceleration (a crash) and opens the SDC.
  • Mounted with the correct orientation and torque, and in a place that experiences chassis loads.
  • Needs a manual reset after triggering.
  • Use a switch rated for the required g-level and confirm what the rulebook requires for your event.

Test: perform a bench "drop/shock" test and verify that it trips and stays latched.


9. BSPD: Brake System Plausibility Device

The BSPD is a standalone safety circuit that opens the SDC if the car is hard braking and delivering significant motor power at the same time.

9.1 What the rules require (2021 EV.7.7, summarized)

  • Opens the SDC when both conditions are true for longer than a set time:
    • Hard braking (brake pressure above a threshold, or equivalent).
    • High motor power (above roughly 5 kW, measured by TS current).
  • Reaction time is about 0.5 s of continuous implausibility.
  • Must be analog/discrete logic. No microcontrollers or programmable logic in the decision path.
  • Must latch and be resettable only manually, not by the driver.
  • Must be tested during tech inspection (by simulating brake pressure and current signals).
  • Must handle sensor fault detection (for example, a short to ground or to the supply on the brake pressure or current signals) and open the SDC.

Thresholds and timing change by year and competition. Check the exact numbers in your current rulebook.

9.2 Typical block diagram

flowchart LR
    BP[Brake pressure sensor] --> CMP1[Comparator: hard braking]
    CUR[TS current sensor] --> CMP2[Comparator: power > threshold]
    CMP1 --> AND[AND gate]
    CMP2 --> AND
    AND --> RC[RC timer ~0.5 s]
    RC --> LATCH[Latch]
    LATCH --> RELAY[SDC relay driver]
    SCS[Sensor short-circuit check] --> LATCH
    RELAY --> SDC[Shutdown circuit]

9.3 Design notes

  • Use comparators (for example LM339-class) plus an RC timing network for the delay.
  • Provide a sensor sanity check that flags a voltage outside the valid range (for example <0.5 V or >4.5 V on a 0.5-4.5 V sensor).
  • Drive a normally-open relay through a low-side MOSFET. The relay only closes when everything is healthy.
  • Document the thresholds, time constants and tolerances on your ESF (Electrical System Form).
  • Provide test points and an inspection test procedure.

BSPD block diagram Figure 4: BSPD architecture.


10. IMD: Insulation Monitoring Device

The IMD continuously monitors insulation resistance between the TS (HV) system and chassis/GLV ground.

10.1 Key requirements

  • Must be a commercially available unit approved for the application (commonly the Bender IR155 series, or equivalent).
  • Insulation threshold: typically ≥ 500 Ω/V of the maximum TS voltage.
  • On fault, it must open the SDC and latch until manually reset.
  • Must not be resettable by the driver.
  • Connected to the TS with the correct measurement leads and chassis ground reference.
  • Status output may drive an IMD indicator light visible to the driver and marshals.

10.2 Example

For a 600 V max accumulator voltage with a 500 Ω/V threshold:

R_min = 500 Ω/V × 600 V = 300 kΩ

The IMD must trip if insulation resistance falls below that value.

10.3 Design tips

  • Keep IMD wiring short, and keep its ground reference connection solid.
  • Make sure the IMD's output is fail-safe (a power loss results in an open SDC).
  • Verify the startup self-test time and account for it in the startup sequence.
  • Test with a known resistor (a "fault injection" resistor) from TS to chassis during validation.

11. AMS / BMS

The Accumulator Management System (battery management system) monitors the accumulator and opens the SDC on a fault.

11.1 What it monitors

  • Cell voltages (over-voltage and under-voltage).
  • Cell temperatures (over-temperature, and sometimes under-temperature for charging).
  • Pack current (over-current).
  • Communications loss between slave boards and the master.
  • Sensor validity.

11.2 Requirements

  • Must be able to open the SDC independently of the VCU.
  • Fault must latch and not be driver-resettable.
  • Provide a clear AMS fault indicator (light).
  • Verify that all cells and temperature sensors required by the rulebook are monitored.

11.3 Design tips

  • Add a hardware watchdog: if the BMS master stops sending "OK", the SDC opens.
  • Use an independent safe output (a relay or an optocoupled "BMS OK" signal) into the loop.
  • Keep thresholds in the cell manufacturer's safe limits, with margin.

12. Interlocks

Interlocks make sure HV cannot be enabled when it would be exposed or unsafe.

Common interlocks:

  • HVD (High Voltage Disconnect) presence or position.
  • Accumulator container lid closed.
  • TS enclosure covers and TS connector mated.
  • Segment maintenance disconnect (SMD) in place where used.

Interlock switches are usually in series in the SDC, near the TSMS. Use NC / positive-break switches so any unplug or open cover opens the loop.


13. Accumulator isolation relays (AIRs)

  • Two relays (AIR+ and AIR-) isolate the accumulator from the rest of the TS.
  • They are normally open, and their coils are powered only through the SDC.
  • Open circuit SDC means AIRs open, so HV is disconnected from the TS.
  • Precharge is performed through a resistor path before the second AIR closes, to limit inrush into motor controller capacitors.

Design considerations

  • Contacts must be rated for the max TS voltage and fault current, including DC breaking capability.
  • Fit flyback protection for the AIR coils (a diode, or the manufacturer's recommendation) without delaying the opening time unacceptably.
  • Use auxiliary contacts for AIR weld detection and feed that to the controller.
  • Economizer circuits (if used) must not allow the AIR to remain closed after the SDC opens.

13.1 Discharge circuit and discharge relay

When the SDC opens, the AIRs isolate the accumulator, but the motor controller / inverter DC-link capacitors (and any other TS capacitance on the load side of the AIRs) stay charged. The discharge circuit bleeds that voltage down so the car is safe to approach and work on.

What the rules require (2021 EV layout, summarized; verify the current numbers):

  • After the SDC opens, the TS voltage on the load side of the AIRs must fall below 60 V DC within 5 seconds.
  • The discharge circuit must be fail-safe: it must work when the SDC is open and when GLV power is lost or the GLVMS is OFF.
  • It must be sized for the maximum TS voltage and be able to survive being connected at that voltage (a commonly quoted requirement is for at least 15 minutes).
  • It must not be active in a way that interferes with normal operation or precharge.
  • The design and discharge time must be documented on the ESF, and the discharge time is measured at tech inspection using the TSMPs.

Typical implementation: normally-closed (NC) discharge relay

 TS+ (load side of AIR+) ───┬─────────────┐
                            │             │
                         [ Motor        [ R_discharge ]
                          controller      │
                          capacitors]   [ Discharge relay, NC contacts ]
                            │             │
 TS- (load side of AIR-) ───┴─────────────┘

 Discharge relay COIL is powered from the SDC (same node as the AIR coils):
   SDC closed (HV allowed)  → coil energized → NC contacts OPEN  → no discharge path
   SDC open / GLV lost      → coil de-energized → contacts CLOSE → resistor bleeds the bus
flowchart LR
    SDC[Shutdown circuit closed] -->|coil energized| DR[Discharge relay contacts OPEN]
    DR --> RUN[Resistor disconnected, normal TS operation]
    SDC2[Shutdown circuit open / GLV lost] -->|coil de-energized| DR2[Discharge relay contacts CLOSED]
    DR2 --> BLEED[Resistor across TS bus, voltage falls below 60 V in under 5 s]

Because the relay is normally closed, any loss of power, broken coil wire or SDC trip results in the discharge path being connected. That is the fail-safe behavior inspectors look for.

Sizing the discharge resistor

The bus decays exponentially: V(t) = V0 · e^(−t / RC).

To reach 60 V in at most t = 5 s:

R ≤ t / ( C · ln(V0 / 60 V) )

Example: V0 = 400 V, C = 500 µF (total TS capacitance, including the inverter)

ln(400 / 60) = 1.897
R ≤ 5 / (500e-6 × 1.897) ≈ 5.27 kΩ

Pick a standard value well below the limit to cover tolerance and capacitance uncertainty (for example 2.2 kΩ to 3.3 kΩ). Then check the thermal side:

Initial power  P0 = V0² / R   = 400² / 3300 ≈ 48 W (peak, decays quickly)
Stored energy  E  = ½ C V0²   = 0.5 × 500e-6 × 400² = 40 J
  • Choose a resistor rated for the voltage, the pulse energy, and repeated cycles (wirewound or aluminum-housed types are common).
  • Mount it where it can dump heat and where a hot resistor can't damage wiring or the accumulator container.
  • If the discharge is connected for a long time (for example, a relay that stays closed with the accumulator still connected through a failed AIR), the resistor must survive the continuous dissipation V² / R. That is why the sizing is a trade-off: low R discharges faster but burns more power in a fault.

Discharge relay selection

Parameter What to check
Contact form Normally closed, or a normally-closed contact block on a contactor
Voltage rating Above max TS voltage, DC rating (not AC)
Breaking current Resistor current at max voltage with margin (it also has to open at V0/R when it is energized)
Coil voltage Matches the SDC voltage (12 V or 24 V)
Coil current Include it in the SDC current budget (Section 15.2)
Pickup/dropout time Must open before or as the AIRs close (see below) and close fast enough to meet the 5 s target
Isolation Coil-to-contact isolation rated for the TS voltage
Mechanical Vibration-rated, sealed, mounted inside the TS enclosure or accumulator container

Timing with the AIRs and precharge

  • At startup, the discharge relay must open before (or at the same instant as) the AIRs close and before precharge starts. Otherwise the precharge current is dumped into the resistor.
  • Power the coil from the same SDC node as the AIR coils so they change state together.
  • Verify on a scope: coil voltage vs. AIR contact state vs. bus voltage, for both startup and shutdown.

Alternatives (check that your rulebook and inspectors allow them)

  • Motor controller internal active discharge: only if it is documented to meet the 60 V / 5 s requirement and still works with GLV off.
  • Always-connected passive resistor: simple and fail-safe, but it wastes power continuously and drains the accumulator through the load-side bus when the AIRs are closed. Usually a poor trade-off for efficiency and heat.
  • Solid-state (MOSFET) active discharge: possible, but the gate drive must be fail-safe (default ON when power is lost). More complex to justify at inspection.
Failure Effect Mitigation
Relay contacts stuck open No discharge, voltage stays high Use a NC relay, test discharge time regularly, monitor bus voltage
Coil powered through a path that survives GLVMS OFF Discharge stays disabled when it should be active Power the coil only from the SDC, never from an always-on rail
Resistor too large Fails the 5 s requirement Size using the formula with margin, measure it
Resistor too small / underrated Overheating or burnt resistor Check pulse energy and fault-case dissipation
Relay closes during precharge Precharge fails or overheats the resistor Verify timing, power the coil from the SDC node
Capacitance underestimated (bigger inverter, extra filters) Discharge slower than calculated Re-measure after any hardware change

Test procedure (bench and tech inspection)

  1. Bring the TS up to the operating voltage (use a reduced voltage first during bench testing).
  2. Measure at the TSMPs with a scope or a data-logging meter.
  3. Open the SDC (press a BRB) and record the time for the voltage to fall below 60 V.
  4. Repeat with: GLVMS OFF, TSMS OFF, and IMD/AMS fault.
  5. Confirm the discharge resistor temperature after repeated cycles.

14. Latching and reset behavior

Device Latching required? Who can reset?
IMD Yes Manual reset, not the driver
AMS Yes Manual reset, not the driver
BSPD Yes Manual reset, not the driver
BOTS Must not reset by repeated operation Cannot be driver-reset
BRB Mechanically latched Pull/twist to reset
Inertia switch Latched Manual

Reset hardware is typically a dedicated button or key-switch accessible from the outside of the car, or a pit-side reset only accessible to team members.

Do not wire any reset through the driver-accessible steering wheel or dash.


15. Wiring, fusing and power budget

15.1 Wiring practice

  • Use automotive-grade wire (for example, TXL/GXL), a gauge suited for the loop current, and proper crimps with strain relief.
  • Keep SDC wiring segregated from TS HV wiring and from noisy motor/inverter wiring.
  • Use locking connectors (Deutsch, Molex MX150 or similar) with pin-lock and clear labeling.
  • Use a distinct wire color for the SDC (many teams choose a dedicated color so it can be traced quickly).
  • Avoid splices; terminate on terminal blocks where possible.

15.2 Power budget

The loop carries only the AIR coil current plus the relay coils of BSPD/IMD/AMS. Typical total is a few amps.

Example:

Load Current @ 12 V
AIR+ coil 0.4 A
AIR- coil 0.4 A
BSPD relay 0.1 A
IMD relay 0.1 A
AMS relay 0.1 A
Total ~1.1 A
  • Size the fuse and switch contacts with margin (>2x).
  • Many rulebooks require you to list SDC current draw on the ESF.

15.3 Fusing

  • Fuse the SDC supply near the source.
  • Make sure fuse rating protects the wiring but doesn't nuisance-trip on relay inrush.

16. Startup sequence

Typical sequence for an EV:

  1. GLVMS ON: GLV system powers up (BMS, IMD, VCU, BSPD).
  2. IMD and BSPD self-checks complete, and fault indicators clear.
  3. BMS reports OK (cells in range, comms alive).
  4. All BRBs released, BOTS and inertia switch closed.
  5. TSMS ON: the SDC loop closes and the AIR coils get power.
  6. Precharge runs; when the voltage reaches the target, the second AIR closes.
  7. TS active indicator turns on.
  8. Ready-to-Drive (RTD) sequence: brake pressed + start button, then the RTD sound plays (about 1-3 s) before the motor controller is enabled.
sequenceDiagram
    participant D as Driver/Team
    participant G as GLVMS
    participant S as SDC
    participant T as TSMS
    participant A as AIRs
    participant P as Precharge
    participant R as RTD
    D->>G: Turn ON
    G->>S: GLV power available
    S->>S: IMD / BSPD / BMS checks pass
    D->>T: Turn ON
    T->>A: Coil power (via SDC)
    A->>P: AIR- closed, precharge starts
    P->>A: Voltage reached, AIR+ closes
    D->>R: Brake + Start button
    R->>D: RTD sound, drive enabled

17. Fault matrix

Fault Detector SDC result Driver indication Recovery
Insulation fault IMD Opens, latched IMD light Fix insulation, manual reset
Cell over-temperature AMS Opens, latched AMS light Cool down, inspect, manual reset
Brake pedal over-travel BOTS Opens None (car stops) Repair brake system
Brake + throttle plausibility BSPD Opens, latched BSPD indicator (if fitted) Resolve cause, manual reset
Crash Inertia switch Opens None Inspect car, manual reset
Emergency stop BRB Opens None Release the BRB
HVD removed / lid open Interlock Opens None Restore the connector or lid
GLV power loss n/a Opens (relays de-energize) Dash dark Restore power
Any SDC opening Discharge relay (NC) Contacts close, TS bus bleeds below 60 V in under 5 s TS active light off Verify with TSMPs before touching

18. Technical inspection checklist

Typical items inspectors check (confirm with your event):

  • SDC schematic submitted on the ESF and matches the car.
  • GLVMS and TSMS: location, color, labeling, key, direct-acting.
  • All three BRBs in place and working.
  • BOTS operates and cannot be reset by repeated operation.
  • Inertia switch present, correctly mounted.
  • BSPD tested using the inspection procedure (simulated brake + current).
  • IMD tested with a known fault resistor.
  • AMS fault test (for example, disconnect a sense wire or simulate over-temperature).
  • Interlocks open the SDC.
  • All SDC elements are in series with no bypass.
  • No programmable logic in the parts where it is prohibited.
  • Latching and reset behavior verified.
  • TS active light and fault lights are working.
  • Discharge circuit: discharge relay is normally closed, coil powered only from the SDC, TS < 60 V within 5 s after SDC opens (also with GLVMS OFF).
  • TSMP voltage checks after SDC open.

19. Common mistakes and failure modes

Mistake Consequence Fix
Normally-open switches used where NC are needed A broken wire reads as "OK" Use NC contacts so a broken wire opens the loop
Software-only BSPD Fails inspection, unsafe if code hangs Implement analog/discrete logic
BRB wiring routed through a connector without positive locking Intermittent shutdowns Use locking connectors and strain relief
IMD ground reference poor False trips or missed faults Short, solid chassis ground connection
Reset accessible to the driver Rule violation Move reset to an external/pit location
Relay coil without flyback protection Voltage spikes damage electronics Add diodes or snubbers
AIR economizer keeps AIR closed after SDC opens Dangerous Verify timing, test with a scope
Under-rated BRB/inertia contacts Contact welding Use contacts rated for the current and inductive load
Missing BMS watchdog A BMS crash leaves the SDC closed Add a hardware watchdog
Undocumented thresholds ESF mismatch at inspection Record values and tolerances

20. Design and validation checklist

Design

  • Write a requirements list straight from the rulebook (with rule numbers).
  • Draw the full SDC schematic with every element, rating and connector.
  • Do a fail-safe review (FMEA): for each wire, connector and component, what happens when it opens or shorts?
  • Define thresholds and timing (BSPD, IMD, AMS).
  • Choose parts with margin (current, voltage, temperature, vibration).
  • Plan test points, indicators and reset hardware.

Bench validation

  • Continuity and polarity check of the full loop.
  • Trip each element individually and confirm the SDC opens.
  • Measure AIR opening time after an SDC trip.
  • BSPD: sweep brake pressure and current, confirm thresholds and delay.
  • IMD: inject a fault resistor, confirm trip and latch.
  • AMS: simulate over-voltage, under-voltage, over-temperature and comms loss.
  • Vibration/connector wiggle test while monitoring SDC voltage.

Vehicle validation

  • Rain/water exposure check on switches and connectors.
  • Full startup/shutdown cycles (10+).
  • Verify the TS discharge and TSMP readings after every shutdown path.
  • Run a mock tech inspection with someone outside the electrical team.

21. Glossary

Term Meaning
SDC Shutdown Circuit
GLV Grounded Low Voltage system (all non-tractive systems)
TS Tractive System (high voltage)
GLVMS Grounded Low Voltage Master Switch
TSMS Tractive System Master Switch
BRB Big Red Button (emergency shutdown button)
BOTS Brake Over-Travel Switch
BSPD Brake System Plausibility Device
IMD Insulation Monitoring Device
AMS / BMS Accumulator / Battery Management System
AIR Accumulator Isolation Relay
TSMP Tractive System Measurement Points
HVD High Voltage Disconnect
Discharge relay Normally-closed relay that connects the discharge resistor across the TS bus when the SDC opens
ESF Electrical System Form
RTD Ready To Drive
SSOK Safety Systems OK

22. Images and references

The image placeholders above (for example images/sdc_overview.png) are local paths. I could not verify stable direct image URLs, and I don't want to give you broken or invented links. To fill them in:

  1. Save screenshots/diagrams into an images/ folder next to this file, or
  2. Replace each path with a direct image URL you have rights to use, for example: ![Alt text](https://your-host.example/path/to/image.png)

Best sources for diagrams:

  • Your rulebook's own schematic figures (for example, the "Shutdown Circuit Schematic" figure in the EV section, or the Formula Hybrid+Electric ESF-2 form figures such as the Safety Shutdown Circuit Schematic and Location of Shutdown Circuit Components).
  • Your team's own CAD/schematics (best option, since it is your actual car).

22.2 Web references (pages with diagrams and explanations)

22.3 Suggested figures to create

Figure Content
Fig. 1 Full SDC schematic (series chain)
Fig. 2 Car layout with component locations
Fig. 3 Master switch mounting and labeling
Fig. 4 BSPD block diagram and thresholds
Fig. 5 IMD wiring (TS+, TS-, chassis reference, output)
Fig. 6 AIR + precharge circuit
Fig. 7 Startup state diagram

Document status: draft. Cross-check every rule number, threshold and timing with the current official rulebook for your competition and year.